Flow Range: 0.0264 - 1.10 GPM, Square Wave (Pulse) Output, 5-24VDC Power Supply Required

DigiflowX3 ULF Sensor

ULF Sensor, Hall Effect


Type ULF
Ultra Low Flow Sensors

FlowX3

The Type ULF Ultra Low Flow Sensors consist of a transducer and a four blade paddle wheel rotor with a permanently mounted magnet inside each blade. A square wave output signal is generated with frequency proportional to the rate of rotor rotation and flow velocity. The Pulse Output is normally fed to a FlowX3 Battery Powered Flow Monitor, or externally powered Flow Monitor/Transmitter, Blind Transmitter, Batch Controller or Adjustable Flow Switch. For simple flow indication, the output can be fed directly to a PLC.

Flow Sensors are available in two styles; Hall Effect, which requires a 5 to 24 VDC power supply and Reed Effect which operates on 3-5 VDC. Coil Effect Sensors are used for all Battery Powered flow monitors. Hall Effect signals can be transmitted up to 984 feet (300 meters) without the need for signal conditioning equipment. Coil Effect signals can be transmitted up to 52 feet (16 meters) with conditioning.

ULF Low Flow Sensor



Polyoxymethylene
(POM) Version

ECTFE (Halar)
Version

Sensor Body: POM ECTFE
Rotor: POM ECTFE
Shaft: Corepoint Sapphire
Bearings: - Sapphire
O-Rings: Viton Viton or Kalrez
Connections:

Inline 1/4" BSP male threaded

Flow Ranges:
ULF 01 0.0066 - 44.0 GPM / 1.5 - 100 LPH
ULF 03 0.0264 - 1.10 GPM / 6 - 250 LPH
Monitors
Monitors/Xmtr
Batch Controllers
Fittings
Flow Sensors


Technical - General:

Output Signal: Square Wave (Pulse)
Electrical Class: NEMA 4, 4X
Accuracy: < 2% of Reading after Field Calibration or + 1.0% of FS
Repeatability: + 0.5% of Full Scale
Viscosity Range: 1 - 10 Centistokes
Max. % of Solids: Clean Service Only, No solids recommended;
Working Temp: 14 to 176' F (-10 to 80'C)
Working Pressure: 70 psi (5 bar) Max @ 72' F
Cable: 22 AWG, 3 Conductor
Technical - ULF.H (Hall Effect) Sensor
Supply Voltage: 5 to 24 VDC regulated
Supply Current: < 15 mA @ 24 VDC
Cable Length: 984' (300m) Maximum

Technical - ULF.R (Reed Effect) Sensor

Supply Voltage: Volt free Reed Contact
Cable Length: 52' ( 16m) Maximum

Integral Mount Instrument
Panel Mount Instrument
Wall Mount Instrument
Installation Guidelines
  • The sensor can be installed in any position, horizontally or vertically, although horizontal is preferred. A non-horizontal installation may cause a greater error on the low side of the flow range;

  • Install the sensor with the flow indicator arrow pointing in the direction of the flow;

  • Maximize the distance between the flow sensor and pumps, valves, elbows, or other obstructions that may cause turbulence at the flow sensor. 6" of straight pipe up and downstream of the flow sensor is suggested.



Dimensions

ULF Sensor Dimensions


Wiring
ULF.H Sensor Connector to FlowX3 Instruments
ULF.H Wiring Diagram
ULF.H Sensor to Other Brand Instruments
ULF.H Wiring Diagram
ULF.R Sensor Connection to FlowX3 and Other Brand Instruments
ULF.R Wiring Diagram

Price: $210.00
Buy Product Online | Visit Store Home
 
Manufactured by Digiflow FlowX3


 Other Items from Low Viscosity

  ULF Sensor, Hall Effect - Flow Range: 0.0066 - 0.44 GPM, Square Wave (Pulse) Output, 5-24VDC Power Supply Required
  ULF Sensor, Hall Effect - Flow Range: 0.0264 - 1.10 GPM, Square Wave (Pulse) Output, 5-24VDC Power Supply Required
  ULF Sensor, Reed Switch  - Flow Range: 0.0066 - 0.44 GPM, Square Wave Output, No Power Supply Required
  ULF Sensor, Reed Switch  - Flow Range: 0.0264 - 1.10 GPM, Square Wave Output, No Power Supply Required

 

  Return To BuyGPI.com - Your GPI Turbine & Oval Gear Flow Meter Store

 

 

e-commerce solutions